02Technical Center

Proof,
not promises.

Every figure on this site states how it was obtained: laboratory tested, calculated, or not yet available. This page is the chain of evidence.

01 — The tested results

Silentium 100: Rw 52 dB.

C −1 · Ctr −4 · Silentium 100 · full assembly

Laboratory tested

Measurement standard
ISO 10140-2
Rating standard
ISO 717-1:2020
Tested specimen
6 + 6 mm laminated glass · air gap · 6 + 6 mm laminated glass
Total construction depth
100 mm
Specimen area
1.85 m²
Laboratory
GiB mbH · Arnstorf, Germany
Accreditation
DAkkS · ISO/IEC 17025 · D-PL-18520-01-00
Report number
E260327M1/1_rev00
Report date
30 March 2026
  • Silentium Alto

    Laboratory tested

    Rw 51 dB

    C −1 · Ctr −4

    12 mm float glass · 60 mm air gap · 6 + 6 mm laminated glass. Report E260413A1/1_rev00, 14 April 2026.

    Read the Silentium Alto test summary

02 — Evidence register

Every published figure, and what stands behind it.

A laboratory result, a calculation and a design target are different things. Each acoustic statement on this site is listed here with its evidence level.

Silentium 100
6 + 6 mm laminated · air gap · 6 + 6 mm laminated
Rw 52 dB (C −1 · Ctr −4)
Laboratory tested

GiB mbH · Report E260327M1/1_rev00 · 30 March 2026

Test summary, Silentium 100, 6 + 6 mm laminated · air gap · 6 + 6 mm laminated

Silentium Alto
12 mm float · 60 mm air gap · 6 + 6 mm laminated
Rw 51 dB (C −1 · Ctr −4)
Laboratory tested

GiB mbH · Report E260413A1/1_rev00 · 14 April 2026

Test summary, Silentium Alto, 12 mm float · 60 mm air gap · 6 + 6 mm laminated

Silentium Alto
10 mm toughened · 60 mm air gap · 10 mm toughened
Rw 45 dB (C −3 · Ctr −5)
Calculated

Prediction · INSUL v9.0.24 · VIBROCOMP ME FZCO · rated to ISO 717-1:2020 · July 2026

System page, Silentium Alto, 10 mm toughened · 60 mm air gap · 10 mm toughened

Forma
Single 6 + 6 mm laminated (13.52 mm)
Rw 36 dB (C 0 · Ctr −1)
Calculated

Prediction · INSUL v9.0.24 · VIBROCOMP ME FZCO · rated to ISO 717-1:2020 · May 2026

System page, Forma, Single 6 + 6 mm laminated (13.52 mm)

Porta
All configurations
No figure published
Not yet tested

No laboratory result exists yet. Data will be published when testing is complete.

System page, Porta, All configurations

Vista
All configurations
No figure published
Not an acoustic system

Specified for transparency or flexibility rather than sound insulation.

System page, Vista, All configurations

Trait
All configurations
No figure published
Not an acoustic system

Specified for transparency or flexibility rather than sound insulation.

System page, Trait, All configurations

Pli
All configurations
No figure published
Not an acoustic system

Specified for transparency or flexibility rather than sound insulation.

System page, Pli, All configurations

03 — Validation framework

Criterion, standard, verification.

Acoustic

Airborne sound reduction, Rw 52 dB measured on the full Silentium 100 assembly

ISO 10140-2 · ISO 717-1:2020

Laboratory tested

Acoustic

Airborne sound reduction, Rw 51 dB measured on the full Silentium Alto assembly

ISO 10140-2 · ISO 717-1:2020

Laboratory tested

Structural

Strength and robustness of the Silentium partition structure, Severe Duty

BS 5234-2

Tested

Glazing

Tempered, heat-soaked toughened, and laminated safety glass

EN 12150 · EN 14179 · EN 14449

Specified

Material

Aluminium alloy 6063-T5 / T6, mill certificate per extrusion batch

EN 573-3 · EN 755-2

Traceable

Surface

Polyester powder coating, minimum 60 µm, Class 2 where specified

Qualicoat Class 2 · EN 12206-1

Specified

Anodising

Architectural anodising, natural to black

EN 12373-1 · QUALANOD

Specified

04 — Hear the difference

Acoustic performance you can understand.

Sound insulation · listening comparison

Reduction
0dB

No partition

DEMO PLAYBACK LEVEL100%

Normal speech and office activity remain clearly audible.

Select rating

Audio demonstration is illustrative. The 52 dB step represents the laboratory-tested Silentium 100; the other steps are generic reference levels for comparison, not Luperal systems. The playback level shown is a property of this demonstration, not a measured value. Actual perceived sound reduction depends on room conditions, flanking paths, installation quality, glass configuration, and the tested complete assembly. Rw ratings are laboratory values measured under controlled conditions; site performance can differ.

05 — Sealing engineering

Sound finds gaps. The system is engineered to close them.

  1. Decoupled construction

    Two independent glass panes with no rigid connection. The air gap interrupts the vibration path instead of carrying it.

  2. Continuous EPDM gaskets

    Acoustic gaskets run unbroken at every glass-to-profile interface, compressed to a controlled line load.

  3. Flanking control

    Isolation pads at floor and ceiling junctions limit sound bypassing the partition through the structure.

  4. Glass configuration logic

    Symmetric and asymmetric laminated builds chosen per requirement. Each build-up carries its own evidence level.

06 — Documents

The evidence, to read and to request.

Test summaries are published here. Full laboratory reports are issued by the engineering team, typically within one working day.

  • Rw 52 dB laboratory test · summary

    Evidence summary · Silentium 100 · 6 + 6 / air gap / 6 + 6 mm laminated · HTML · 30 March 2026

    Result, standards, specimen, laboratory, accreditation and scope of the test.

  • GiB test report E260327M1/1_rev00

    Acoustic test report · Silentium 100 · tested specimen · PDF · rev00 · 30 March 2026

    Full laboratory report. Issued to architects and consultants on request.

  • Rw 51 dB laboratory test · summary

    Evidence summary · Silentium Alto · 12 / 60 / 6 + 6 mm · HTML · 14 April 2026

    Result, standards, specimen, laboratory, accreditation and scope of the test.

  • GiB test report E260413A1/1_rev00

    Acoustic test report · Silentium Alto · tested specimen · PDF · rev00 · 14 April 2026

    Full laboratory report. Issued to architects and consultants on request.

07 — Technical FAQ

The questions consultants actually ask.

Is the Rw 52 dB rating for the glass or for the system?

For the complete system. The figure was measured on the full Silentium 100 assembly, profiles, gaskets, double glazing, and junctions, according to ISO 10140-2, and rated according to ISO 717-1:2020. Glass-only ratings routinely overstate what a built partition achieves.

What does Rw 52 dB mean in practice?

Rw is a laboratory rating of how much airborne sound the partition itself reduces. Rw 52 dB is a high, specification-grade level, suitable for confidential meeting rooms and executive interiors. The separation achieved in a finished room also depends on the floor, ceiling and façade junctions and on any door in the wall, so site values are normally lower than laboratory values.

Do all Luperal systems achieve Rw 52 dB?

No, and we will not claim otherwise. Rw 52 dB is the laboratory result for the tested Silentium 100 configuration. Silentium Alto is laboratory tested at Rw 51 dB with an asymmetric glazing build-up. Forma is single-glazed: its Rw 36 dB is a calculated figure for 6 + 6 mm laminated glass, not a laboratory test. The Porta door-set has not yet been laboratory tested, and the sliding and folding systems carry no published rating.

What is the difference between tested and calculated?

Laboratory tested: Measured on the complete assembly at an accredited laboratory. Report reference published. Calculated: Predicted by an independent acoustic consultant using recognised modelling software. Not a laboratory measurement. Every figure on this site is labelled with one of these evidence levels.

Can we review the test reports before specifying?

Yes. A summary of each laboratory test is published on this site, and the full reports, E260327M1/1_rev00 for Silentium 100 and E260413A1/1_rev00 for Silentium Alto, issued by GiB mbH under DAkkS accreditation D-PL-18520-01-00, are sent to architects and consultants on request, typically within one working day.

What documentation is available for tender packages?

Technical data sheets, CAD section details, specification clauses, acoustic test reports, finish samples, and structural performance statements, prepared at the level required for formal consultant submission. The Documents page lists each one with its access status.